Počet záznamů: 1
Solubility of nitrogen in one-component refrigerants: Prediction by PC-SAFT EoS and a correlation of Henry's law constants
- 1.0369774 - ÚT 2012 RIV GB eng J - Článek v odborném periodiku
Vinš, Václav - Hrubý, Jan
Solubility of nitrogen in one-component refrigerants: Prediction by PC-SAFT EoS and a correlation of Henry's law constants.
International Journal of Refrigeration. Roč. 34, č. 8 (2011), s. 2109-2117. ISSN 0140-7007. E-ISSN 1879-2081
Grant CEP: GA AV ČR IAA200760905; GA ČR(CZ) GPP101/11/P046; GA ČR(CZ) GAP101/11/1593
Výzkumný záměr: CEZ:AV0Z20760514
Klíčová slova: equation of state * nitrogen * non-condensable gas * refrigerant
Kód oboru RIV: BJ - Termodynamika
Impakt faktor: 1.817, rok: 2011
http://www.sciencedirect.com/science/article/pii/S0140700711001630
Even small amount of non-condensable gas e mostly air or nitrogen e present inside a compression refrigerating circuit may decrease the efficiency of the cooling system. So far, a quantitative assessment of the effect of dissolved gases on the cooling circuit performance is hindered by unavailability of suitable thermodynamic models. In this study, we analyzed the solubility of nitrogen in the following refrigerants: hydrochlorofluorocarbons (HCFC) R22, R123, R124; hydrofluorocarbons (HFC) R23, R32, R125, R134a; perfluorocarbons (PFC) R14, R116, R218, R-3-1-10; and hydrocarbons (HC) R290, R600a. Perturbed-Chain (PC) Statistical Associating Fluid Theory (SAFT) and its modification for polar fluids PCP-SAFT were used to model the temperature dependence of the Henry’s law constant of nitrogen. A simple correlation of the Henry’s law constants valid over large temperature ranges was developed, suitable for assessment of the adverse effects of dissolved nitrogen (and approximately air) on the performance of compression cooling systems.
Trvalý link: http://hdl.handle.net/11104/0203765
Počet záznamů: 1