    Direct Measurements of the Volume Flow Rate and Emissions in a Large Naturally Ventilated Building.
    Sensors. Roč. 20, č. 21 (2020), č. článku 6223. ISSN 1424-8220. E-ISSN 1424-8220
    Institucionální podpora: RVO:61388998
    Klíčová slova: boundary layer wind tunnel * air exchange * laser Doppler anemometer * flame ionization detector * dairy barn
    Obor OECD: Meteorology and atmospheric sciences
    Impakt faktor: 3.576, rok: 2020
    Způsob publikování: Open access
    https://www.mdpi.com/1424-8220/20/21/6223/htm

    The direct measurement of emissions from naturally ventilated dairy barns is challenging due to their large openings and the turbulent and unsteady airflow at the inlets and outlets. The aim of this study was to quantify the impacts of the number and positions of sensors on the estimation of volume flow rate and emissions. High resolution measurements of a naturally ventilated scaled building model in an atmospheric boundary layer wind tunnel were done. Tracer gas was released inside the model and measured at the outlet area, using a fast flame ionization detector (FFID). Additionally, the normal velocity on the area was measured using laser Doppler anemometry (LDA). In total, for a matrix of 65 × 4 sensor positions, the mean normal velocities and the mean concentrations were measured and used to calculate the volume flow rate and the emissions. This dataset was used as a reference to assess the accuracy while systematically reducing the number of sensors and varying the positions of them. The results showed systematic errors in the emission estimation up to +97%, when measurements of concentration and velocity were done at one constant height. This error could be lowered under 5%, when the concentrations were measured as a vertical composite sample.
    Trvalý link: http://hdl.handle.net/11104/0315111

     
     
Počet záznamů: 1  

  Tyto stránky využívají soubory cookies, které usnadňují jejich prohlížení. Další informace o tom jak používáme cookies.